Language

Tested and field proven, the Mobile Wastewater Treatment Plant (MWWTP) is a turnkey modular wastewater treatment system that can handle the toughest site conditions. Designed for remote camps and rapid deployments, this system offers nonstop performance with minimal downtime and low power consumption. This multistage modular treatment system can treat 50m3/day (200 people) within two 40' modified shipping containers. Expansion is easily accommodated with the addition of a second MWWTP unit (one 40’ modified shipping container) to double treatment capacity to 400 people in less than eight hours.

The BluMetric advantage includes:

  • State of the art advanced membrane-based filtration built into a containerized solution, manufactured in a quality controlled environment and factory tested;
  • Complete plug and play system and solution;
  • Designed for all climate zones;
  • Easy set-up and operation make this the optimal solution for remote camps and rapid deployments;
  • No infrastructure or buildings required;
  • Rapid installation, simply connect the pipes and electrical supply;
  • Rapid dismantling and cleaning, the best option for relocation and your next mission;
  • Modular design allows for quick and easy expansion to serve camps of 200 to 800 people;
  • Fully enclosed and contained, with integrated spill prevention and a quiet operation;
  • 24/7 service and support.

Focus On – Mobile Wastewater Treatment Plant brochure (PDF)

Design Parameters:

Parameter Design Value Phase 1 Design Value Phase 2 Unit
Per Capita Design Flow 250 250 L/p/d
Number of Persons 200 400 people
Average Daily Flow (ADF) 50 100 m3/d
Peak Instantaneous Inlet Flow 8.3 16.6 m3/h
Site Power Three-Phase, 347/600VY, 60Hz, FLA 127A
System Area Classification According to NFPA 820, 2016 Edition
Ambient Temperatures -40 to 35 -40 to 35 °C
Elevation 100 100 m

Wastewater Characteristics:

Parameter Design Value Unit
Biochemical Oxygen Demand (BOD5) 400 mg/L
Total Suspended Solids (TSS) 250 mg/L
Total Phosphorus (TP) 10 mg/L
Fat, Oil and Grease (FOG) < 30 mg/L
Water Temperature 15 to 25 °C
Alkalinity - mg/L as CaCO3

Effluent Quality:

Parameter Design Value Unit
pH 6.5 to 8.5 -
Biochemical Oxygen Demand (BOD5) < 5 mg/L
Carbonaceous BOD (CBOD5) < 5 mg/L
Total Suspended Solids (TSS) < 1 mg/L
Total Coliform < 200 °CCFU/100ml
Scroll to Top